Services, 20ma output object (class id 32ah), Class attributes – Rockwell Automation 1440-TPS02-01RB XM-320 Position Module User Manual
Page 114: 20ma output object (class id 32a
![background image](/manuals/581430/114/background.png)
Publication GMSI10-UM005C-EN-P - May 2010
106 DeviceNet Objects
Services
1
Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.
4-20mA Output Object
(Class ID 32A
H
)
The 4-20mA Output Object models the configuration of a 4-20mA output
signal.
Class Attributes
The 4-20mA Output Object provides no class attributes.
11
Get/Set
Target Angle
REAL
The angle of the target
relative to the shaft in
degrees.
0 to 90 degrees
12
Get/Set
Upscale
BOOL
Indicates the movement
of the target relative to
the transducer which is
considered positive
displacement.
0 = Away
1 = Towards
13
Get/Set
DC Bias Time
Constant
REAL
The time constant value
used for exponential
averaging of the DC Bias
value (a low pass
filter/output smoothing
filter).
Seconds
14
Get/Set
Name
STRING2
A name to help identify
this transducer or
channel.
18 characters maximum
Table C.38 Transducer Object Instance Attributes
Attr ID
Access
Rule
Name Data
Type
Description
Semantics
Table C.39 Transducer Object Services
Service
Code
Class/Instance Usage
Name
Description
0E
h
Instance
Get_Attribute_Single
Returns a single attribute.
10
h
Instance
Set_Attribute_Single
Sets a single attribute.
1