Rockwell Automation 2706-LV2P_LV2R_LV4P_LV4R DL40 PLUS USER MANUAL User Manual
Page 88
Parallel Port Communications
7–8
Publication 2706-6.1
Override Slave Address Selected as a Message Attribute
The Message/Variable/Slave Run mode allows runtime override of
the slave address specified in the “Send to Slave” message attribute.
To send a message to a slave, Port Use of the RS-485 or RS–232 Port
must be set to DL Slaves.
Triggering Rules
•
Optional slave address must always precede the message number.
•
Up to 10 variables are addressable within a message.
•
Variables must always follow the message number.
•
Variables are always associated with the last message triggered:
–
if the message is in the queue, variables are put into the queue
(with the message) and onto the Historical Events Stack.
–
if the message is running and the variable is displayed, the
variable is updated with the latest data and the data is put onto
the Historical Events Stack.
–
if the message is running and the variable is no longer shown
(as in a scrolling message), new data is not shown but is put
on the Historical Events Stack.
–
if the message is finished running, new data is lost to the
display and to the Historical Events Stack.
•
BCD Sign Bit – Only valid for
[CTRL][V]
BCD variables; not
valid for
[CTRL][W
]
BCD.
– Set = –
– Clear
= +
–
Sign bits must precede variables. The sign cannot be changed
without resending the variable.
–
Bit 0 = Variable l
–
Bit 1 = Variable 2, etc.
–
Bits 9 through 15 ignored
–
No Sign Bit sent (default) = +
Note: For BCD variables only. Ignored for binary and ASCII
variables. To sign a binary variable, use 2’s complement.