Installation and Wiring

9–11

Publication 2706-6.1

When the RS-485 port is configured for Open protocol
communications, the RS-485 port connects one or multiple DL40
Plus displays to a host controller (PLC, SLC, computer, etc) for
serial message triggering. This RS-485 network link supports
multi-drop communications with up to 127 DL40 Plus displays on
the link. We recommend you use Belden 9842 cable at a maximum
length of 4,000 ft (1219 meters).

The following diagram shows a typical RS-485 network with
multiple DL40 Plus displays.

COM

Belden 9842 Cable
Recommended

CH. A

CH. B

To Host Controller

To Next Node

RS-485

Shield

COM

CH. A

CH. B

Shield

COM

CH. A

CH. B

Twisted Pair

User installed jumper at first
and last DL40 Plus (physical
location) on the RS-485 link.

User installed jumper at any
one node only on the RS-485 link

User installed jumper at first
and last DL40 Plus (physical
location) on the RS-485 link.

First DL40 Plus On Network

Last DL40 Plus On Network

1 - E GND

2 - SHLD

3 - COMM

4 - CH A

5 - CH B

6 - TERM

RS-485

1 - E GND

2 - SHLD

3 - COMM

4 - CH A

5 - CH B

6 - TERM

Connecting the RS-485 Port
for Open Protocol