Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 330
Chapter
Call Routines 69–127
13
13 -72
Code
Indicates
0
transfer OK
1
transmission failed
2
enquiry time out
3
•
with handshaking selected – either a loss of CTS signal
while transmitting or a fatal transmitter failure occurred
•
without handshaking selected – a fatal transmitter failure
occurred
4
transmission failure due to modem disconnection (DCD signal
loss for more than 10 seconds) if modem handshaking with
constant carrier is selected
5
DF1 driver is not enabled
6
message timed out
81
illegal command or format
82
host has a problem and will not communicate
83
remote station host is not there, disconnected, or shut down
84
host could not complete function due to hardware fault
85
addressing problem or memory protect rungs
86
function disallowed due to command protection selection
87
processor is in Program mode
88
compatibility mode file missing or communication zone problem
89
remote station cannot buffer command
8B
remote station problem due to download
8C
local station cannot execute command due to active IPBs
C1
illegal address format – field has an illegal value
C2
illegal address format – not enough fields specified
C3
illegal address format – too many fields specified
C4
illegal address format – symbol not found
C5
illegal address format – symbol is 0 or greater than the
maximum number of characters supported by this device
C6
illegal address – address does not exist or does not point to
something usable in this command
C7
illegal size – file is wrong size; address is past end of file
C8
cannot complete request
C9
data or file is too large
CA
request is too large; transaction size plus word address is too
large
CB
access denied, privilege violation
CC
resource is not available; condition cannot be generated
CD
resource is already available; condition already exists
CE
command cannot be executed
CF
overflow; histogram overflow
D0
no access
D1
illegal data type information
D2
invalid parameter; invalid data in search or command block
D3
address reference exists to deleted area
D4
command execution failure for unknown reason; PLC–3
histogram overflow