Input and output arguments – Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 280
Chapter
Call Routines 69–127
13
13 -22
Use CALL 91 to write up to 40 words starting at word 100 of the BASIC
module output buffer to the remote DH-485 data file at the designated node
address, file number, file type, and element offset.
Input and Output Arguments
This routine has six input arguments and one output argument.
Argument
Description
Page
input 1
node address of the remote device (0–31)
13 -22
input 2
file number on the remote device (0–255)
13 -22
input 3
file type written to the remote device
13 -22
input 4
starting element offset within the file on the remote
device (0 to 32767)
13 -23
input 5
number of elements to be transferred
13 -23
input 6
message time-out value
13 -23
output 1
call status
13 -24
Input Argument One
The first input argument is the node address of the remote device (1 to 31).
If the number is not within the range 1 to 31, then the output argument
equals 10, and the write message does not take place.
Input Argument Two
The second input argument is the file number on the remote device (0 to
255). If the number is not within the range 0 to 255, then the output
argument equals 11, and the write message does not take place.
Input Argument Three
The third input argument is the file type written to the remote device.
If the file type is not one of the valid types listed in the table, then the
output argument equals 241, and the write message does not take place.
File type
File type code
Words/Element
integer file
ASC(N)
1 word/element
status file
ASC(S)
1 word/element
counter file
ASC(C)
3 words/element
timer file
ASC(T)
3 words/element
bit file
ASC(B)
1 word/element
control file
ASC(R)
3 words/element
CALL 91: Write BASIC
Output Buffer to Remote
DH-485 Data File