Rockwell Automation 1771-DB BASIC MODULE User Manual
Page 288
Chapter
Call Routines 69–127
13
13 -30
Output Argument One
The output argument specifies the status of the message instruction.
Upon return from the call, the output argument has this definition.
Decimal
output
Hexadecimal
output
Description
0
00
successful completion
2
02
target node cannot accept the message at this time
3
03
target node cannot respond because message is too
large
4
04
target node cannot respond because it does not
understand the command parameters
5
05
BASIC module is off-line (not on link)
6
06
target node cannot respond because requested function
is not available
7
07
target node does not respond
10
0A
BASIC module detects illegal target node address
11
0B
BASIC module detects illegal file number
12
0C
BASIC module detects illegal target file element offset
13
0D
BASIC module detects illegal target file length
14
0E
BASIC module detects illegal time-out value
16
10
target node cannot respond because of incorrect
command parameters or unsupported command
55
37
message timed out (time-out value exceeded)
80
50
target node is out of memory
96
60
target node cannot respond because file is protected
231
E7
target node cannot respond because length requested
is too large
235
EB
target node cannot respond because target node denies
access
236
EC
target node cannot respond because requested function
is currently unavailable
241
F1
BASIC module detects illegal target file type
250
FA
target node cannot respond because another node is
file owner (has sole file access)
251
FB
target node cannot respond because another node is
program owner (has sole access to all files)