Specifications, Appendix, 1769-adn specifications – Rockwell Automation 1769-ADN Compact I/O 1769-ADN DeviceNet Adapter User Manual
Page 153: Series a adapters general specifications
1
Publication 1769-UM001B-EN-P - October 2002
Appendix
A
Specifications
Read this appendix to learn about the 1769-ADN specifications.
1769-ADN Specifications
Series A Adapters General Specifications
Specification
Value
Dimensions
118mm (height) x 87mm (depth) x 50mm (width)
height including mounting tabs is 138mm
4.65in (height) x 3.43in (depth) x 1.97in (width)
height including mounting tabs is 5.43in
Approximate Shipping Weight
(With Carton)
280g (0.61lbs)
Storage Temperature
-40 to +85C (-40F to +185F)
Operating Temperature
0 to +60C (+32F to +140F)
Operating Humidity
5 to 95% non-condensing
Operating Altitude
2000m (6561ft)
Vibration
Operating: 10 to 500Hz, 5G, 0.030in max. peak-to-peak
Relay Operation: 2G
Shock
Operating: 30G, 11ms panel mounted
(20G 11ms DIN-rail mounted)
Relay Operation: 7.5G panel mounted
(5G DIN-rail mounted)
Non-Operating: 40G panel mounted
(30G DIN-rail mounted)
Agency Certification
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C,
D (UL 1604, C-UL under CSA C22.2 No. 213)
Radiated and Conducted
Emissions
EN50081-2 Class A
Electrical/EMC
The adapter has passed testing at the following levels:
• ESD Immunity
(IEC1000-4-2)
4kV contact, 8kV air, 4kV indirect
• Radiated Immunity
(IEC1000-4-3)
10V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
• Fast Transient Burst
(IEC1000-4-4)
2kV, 4 kHz
• Surge Immunity
(IEC1000-4-5)
2kV galvanic gun
• Conducted Immunity
(IEC1000-4-6)
10V, 0.15 to 80 MHz
1
1. Conducted immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is
30 MHz to 1000 MHz.