Module Addressing

Addressing is changed from two modules with 4 channels to one
module with 8 channels. The output addressing is shown below.

Analog Conversion

The following information is provided for reference only; the
1746-NO8 is directly compatible with the 1746-NO4 when used in
Class 1 mode.

The 1746-NO8 converts a 16-bit two’s complement binary value into
an analog output signal using a 16-bit converter.

In 1746-NO4 compatible mode (e.g. Class 1), the 14 most significant
bits are used, as the 1746-NO4 uses a 14 bit converter.

The following tables identify the current and voltage output ranges for
the output channels, and their resolution when using 1746-NO4
compatible mode.

1746-NO4 Output Addressing

O:3.0 - Slot 3, Channel 0 Data Word

O:4.0 - Slot 4, Channel 0 Data Word

O:3.1 - Slot 3, Channel 1 Data Word

O:4.1 - Slot 4, Channel 1 Data Word

O:3.2 - Slot 3, Channel 2 Data Word

O:4.2 - Slot 4, Channel 2 Data Word

O:3.3 - Slot 3, Channel 3 Data Word

O:4.3 - Slot 4, Channel 3 Data Word

1746-NO8 Output Addressing

O:3.0 - Slot 3, Channel 0 Data Word

O:3.4 - Slot 3, Channel 4 Data Word

O:3.1 - Slot 3, Channel 1 Data Word

O:3.5 - Slot 3, Channel 5 Data Word

O:3.2 - Slot 3, Channel 2 Data Word

O:3.6 - Slot 3, Channel 6 Data Word

O:3.3 - Slot 3, Channel 3 Data Word

O:3.7 - Slot 3, Channel 7 Data Word

Table B.2 1746-NO8I and 1746-NO4I Output Range

Current Range

Decimal Representation for
Output Word

Resolution per LSB

0 to 21 mA

0 to 32,764

2.56348 A

0 to 20 mA

0 to 31,208

4 to 20 mA

6,242 to 31,208

N
O

4

N

O

4

SLOT 0 1

2

3

4 5

6

N
O

8

SLOT 0

1 2

3

4

5 6