Module Diagnostics and Troubleshooting 6-5

Troubleshooting

Figure 6.2 Problem Resolution Flowchart

Check that module
is properly seated
in chassis.
Cycle power.

Module
fault
condition.

Module
Status
LED off.

Module
Status
LED flashing.

Module
Status
LED on.

1

Flash

2

Flashes

3

Flashes

4

Flashes

5

Flashes

6

Flashes

7

Flashes

24V Power Failure

Check external supply or

jumper settings (if used).

Configuration Error

Check module and channel

configuration settings.

EEPROM Fault

RAM Fault

Input Access Error

Output Access Error

ROM CRC Failure

Is problem
corrected?

Yes

No

Is problem
corrected?

Yes

No

End

End

End

Contact RA Technical

Support or your

Allen-Bradley

distributor.

Contact RA Technical

Support or your

Allen-Bradley

distributor.

Check LEDs

on module.

Channel

Status LED(s)

flashing.

Channel

Status LED(s)

off.

Channel

Status LED(s)

on solid.

Channel is

enabled, but
not working.

Channel is

not enabled.

Fault

condition.

Check channel

status word

bits 12 to 15.

Enable channel.

Set configuration

word, bit 0 = 1.

Retry.

Check channel

status word 1

bits 12 to 15.

Bit 15

set (1)

Bit 15

set (1)

Bit 14

set (1)

Bit 13

set (1)

Bit 12

set (1)

Fatal channel error. Reset
the processor or cycle
power to the module.

The processor or module
is resetting. Check SLC
processor status.

Current loop for this
channel is open.

24V Power Failure.
Check external supply.

Check channel

status word 2

bit 15.

Channel configuration
error. Check channel
configuration.