5-4 I/O Data and Status Information

Input Status Words

Channel Input Status Word 1 (Class 1 and Class 3)

Words 0 through 7 of the input image file (addresses I:e.0 through
I:e.7) reflect the configuration and status of each channel. Use the data
provided in these status words to determine various channel
conditions. Input Status 1 addressing and bit definitions are shown in
the following figures:

Figure 5.3 Input Status 1

Input Image Words 0 through 7

Function

Input Status 1

Cl

ass 1

and Cl

ass

3

I:e.0

Channel 0

I:e.1

Channel 1

I:e.6

Channel 6

I:e.7

Channel 7

Table 5.3 Input Status 1 Word Details

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Output channel disable
Output channel enable

0
1

1746-NO8V Output Ranges:
±10V dc
1 to 5V dc
0 to 5V dc
0 to 10V dc

0
0
1
1

0
1
0
1

1746-NO8I Output Ranges:
0 to 21 mA
4 to 20 mA
0 to 20 mA
Invalid

0
0
1
1

0
1
0
1

Invalid

0

1746-NO4 compatible format
Engineering units
Scaled for PID
Proportional counts
User-defined scale
Invalid
Invalid
Invalid

0
0
0
0
1
1
1
1

0
0
1
1
0
0
1
1

0
1
0
1
0
1
0
1

Invalid

0

0

0

0

0

24V Power Failure

1

Current Loop Open

1

Module/SLC Resetting

1

Fatal Channel Error

1