Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual
Page 134

134
Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
134 Software Configuration Tags
O.Total[1].Control
Binary
SINT
O.Total[1].Reset
Decimal
BOOL
O.Total[1].Load
Decimal
BOOL
O.Total[1].ProverEnable
Decimal
BOOL
Enables the prover operation on output connected to
channel 1. Once this bit is enabled, the module waits
for output Z
0
to energize before beginning prover
operations.
0 = Prover operation is disabled
1 = Prover operation is enabled
O.Total[1].FillEnable
Decimal
BOOL
Enables the filling operation on output connected to
channel 1.
0 = Fill operation is disabled
1 = Fill operation is enabled.
O.Total[1].FillStart
Decimal
BOOL
Begins filling operation when Fill Enable is enabled on
output connected to channel 1.
0 = Do not begin filling
1 = Begin filling
O.Total[1].FillHold
Decimal
BOOL
Holds/pauses filling operation on output connected to
channel 1.
0 = Continue filling operation
1 = Hold/pause filling operation
O.Total[1].RollOverValue
Decimal
DINT
Sets the user-defined rollover value on output
connected to channel 1.
Range of 0 - 2,147,483,647
O.Total[1].CombinedCorrectionFactor
Float
REAL
Unitless factor that is multiplied by Gross Rate with
results shown as NetRate of channel 1.
This value must be set to 1.0 when not used or gross
rate will be 0.
Calculation Type must be set to 0 to use this factor.
O.Total[1].BaseTemperature
Float
REAL
Temperature in °F of output connected to channel 1.
O.Total[1].FlowingTemperature
Float
REAL
Temperature in °F of output connected to channel 1.
O.Total[1].AtmosphericPressure
Float
REAL
Pressure in psia of output connected to channel 1.
O.Total[1].StaticGaugePressure
Float
REAL
Pressure in psig of output connected to channel 1.
O.Total[1].BasePressure
Float
REAL
Pressure in psig of output connected to channel 1.
O.Total[1].BaseCompressibility
Float
REAL
Default = 1
O.Total[1].FlowingCompressibility
Float
REAL
Default = 1
O.Total[1].FillTotalTarget
Float
REAL
Target for Fill Complete, except when Fill Transition is
greater than this value.
O.Total[1].FillTransition
Float
REAL
When fill cycle is started, trickle flow is initiated when
the Fill Total is equal to or greater than this value. Full
flow is initiated when the Fill Total is less than this
value.
Table 15 - Configurable Flowmeter Module Output Tags
Name
Style
Data type
Definition