106 Configuring the Configurable Flowmeter Module
O.Total[0].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output
connected to channel 0. When the Speed
exceeds the Highest Allowed Frequency
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
O.Total[0].Acceleration
Decimal
BOOL
Enables the Acceleration alarm on output
connected to channel 0. When the absolute
acceleration exceeds the Acceleration
Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
1
I.Status[0].ProverState
Decimal
SINT
Displays status of the prover operation on
channel 0
0 = Prover Not Active
1 = Prover waiting for 1
st
start
2 = Prover waiting for 1
st
stop
3 = Prover waiting for 2
nd
start
4 = Prover waiting for 2
nd
stop
5 = Prover Complete
I.Status[0].TotalCounts
Decimal
DINT
Displays actual pulses counted by the
counter connected to the channel 0
I.Status[0].FreqAverage
Float
REAL
Displays frequency averaged over the Meter
samples on channel 0
I.Status[0].FreqPeriod
Float
REAL
Displays frequency using sample time on
channel 0
I.Status[0].Speed
Float
REAL
Displays frequency using filter resolution on
channel 0
I.Status[0].Acceleration
Float
REAL
Displays acceleration on channel 0 as
calculated by using AccelCalculation
samples
I.Status[0].GrossVolume
Float
REAL
Total Counts during each
Sample/K-factor x Meter Factor as occurs on
channel 0
I.Status[0].NetVolume
Float
REAL
Total Counts during each
Sample/K-factor x MeterFactor x CCF) as
occurs on channel 0
I.Status[0].GrossRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x
Sample Interval) x Meter Factor as occurs on
channel 0
I.Status[0].NetRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x
Sample Interval) x Meter Factor x CCF as
occurs on channel 0
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name
Style
Data type
Definition
Enter this