128 Software Configuration Tags
Input Tags
You must use the Input tags to monitor CFM module status.
Table 14
lists and
defines CFM Input tags:
C.OutputSetup[1].DynamicError
Decimal
SINT
Sets the state of output 1 when a dynamic error occurs
0 = Continue operation
1 = Reset Output 0 to OFF on Error
2 = Set Output 0 to ON on Error
C.OutputSetup[1].TriggerOn
Decimal
SINT
Sets when output 1 energizes
0 = No Action
1 = Frequency
2 = Acceleration
3 = Full Flow State
4 = Trickle Flow State
5 = Prover Run State
6 = Prover Range State
C.OutputSetup[1].TieToCounter
Ties a channel to output 1
0 = No connection
1 = Connect Channel0 to Output 1
2 = Connect Channel1 to Output 1
Table 13 - Configurable Flowmeter Module Configuration Tags
Name
Style
Data type
Definition
Table 14 - Configurable Flowmeter Module Input Tags
Name
Style
Data type
Definition
I.Fault
Hex
DINT
Display if a fault has occurred on the module.
0 = no fault has occurred
1 = a fault has occurred
I.ChannelStatus
Hex
DINT
I.Output0State
Decimal
BOOL
Displays the state of output 0
0 = OFF
1 = ON
I.Output1State
Decimal
BOOL
Displays the state of output 1
0 = OFF
1 = ON
I.Output0IsOverridden
Decimal
BOOL
Displays whether output 0 was manually overridden
0 = output was not overridden
1 = output was overridden
I.Output1IsOverridden
Decimal
BOOL
Displays whether output 1 was manually overridden
0 = output was not overridden
1 = output was overridden
I.Ch0WasReset
Decimal
BOOL
Displays whether channel 0
was reset
0 = output was not reset
1 = output was reset