Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
102 Configuring the Configurable Flowmeter Module
4. Change only the tags listed in
Table 8
. Ignore all other tags; they do not
affect totalizer mode prover function.
Table 8 - Tag Changes Required for Totalizer Mode Using Prover Function
Name
Style
Data type
Definition
Enter this
Value
C.ProgToFaultEn
Decimal
BOOL
Sets outputs to selected Fault state when
the owner-controller is in Program mode.
0 = outputs use Program mode setting
1 = outputs use fault mode settings
0
C.Operations[0].FilterControl.0
Decimal
SINT
bit 0 = 1 - apply filter to F0
bit 1 = 1 - apply filter to G0
bit 2 = 1 - apply 1second debounce to G0
0
C.Operations[0].MeterSamples
Decimal
SINT
50
C.Operations[0].ThresholdControl
Decimal
SINT
Sets flowmeter input threshold control
0 = 50mV threshold (magnetic pickup)
1 = 1.3V threshold (TTL)
2 = 4.0V threshold (PreAmp)
0
C.Operations[0].CalculationType
Decimal
SINT
Sets calculation type
0 = Counts/K-factor x MeterFactor correction
x CCF
1 = Counts/K-factor x MeterFactor correction
x AGA 7 compensation or CCF if CCF is not
equal to 0.0
0
C.Operations[0].AccelCalculation
Decimal
SINT
Number of past samples to use to calculate
an acceleration value.
Sample range is 0 to 255.
50
C.Operations[0].MinDetectableFreq
Float
REAL
User-defined value from 0 - 120,000.
Sets FreqAverage, FreqPeriod, Speed,
GrossRate, and NetRate reading to 0 when
calculated value is less than value entered.
GrossVolume, and NetVolume do not
increment below this value even though
TotalCounts increments over time.
5
C.Operations[0].HighestAllowedFreq
Float
REAL
User-defined value between
MinDetectableFreq and 120,000
When the frequency reaches this level, it
sets the overspeed alarm limit
3700
C.Operations[0].AccelAlarmValue
Float
REAL
Sets Acceleration alarm limit
-Maximum acceleration (cycles per second
2
)
2
)
100