Rockwell Automation 1756-CFM ControlLogix Configurable Flowmeter Module User Manual
Page 133
133
Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
Software Configuration Tags 133
O.Total[0].RollOverValue
Decimal
DINT
Sets the user-defined rollover value on output
connected to channel 0.
Range of 0 - 2,147,483,647
O.Total[0].CombinedCorrectionFactor
Float
REAL
Unitless factor that is multiplied by Gross Rate with
results shown as NetRate of channel 0.
This value must be set to 1.0 when not used or gross
rate will be 0.
Calculation Type must be set to 0 to use this factor.
O.Total[0].BaseTemperature
Float
REAL
Temperature in °F of output connected to channel 0
O.Total[0].FlowingTemperature
Float
REAL
Temperature in °F of output connected to channel 0
O.Total[0].AtmosphericPressure
Float
REAL
Pressure in psia of output connected to channel 0
O.Total[0].StaticGaugePressure
Float
REAL
Pressure in psig of output connected to channel 0
O.Total[0].BasePressure
Float
REAL
Pressure in psig of output connected to channel 0
O.Total[0].BaseCompressibility
Float
REAL
Default = 1
O.Total[0].FlowingCompressibility
Float
REAL
Default = 1
O.Total[0].FillTotalTarget
Float
REAL
Target for Fill Complete, except when Fill Transition is
greater than this value.
O.Total[0].FillTransition
Float
REAL
When fill cycle is started, trickle flow is initiated when
the Fill Total is equal to or greater than this value. Full
flow is initiated when the Fill Total is less than this
value.
O.Total[0].FillTransitionTimer
Float
REAL
When timed trickle flow is selected, the status remains
ON for this time during this state.
The value must be changed prior to entering the trickle
flow state.
O.Total[1].AlarmEnables
Binary
SINT
O.Total[1].Overrange
Decimal
BOOL
Enables the Overrange alarm on output connected to
channel 1. When the Frequency Period exceeds 100KHz,
this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Overflow
Decimal
BOOL
Enables the Overflow alarm on output connected to
channel 1. When the Total Counts exceeds the Roll Over
value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Overspeed
Decimal
BOOL
Enables the Overspeed alarm on output connected to
channel 1. When the Speed exceeds the Highest
Allowed Frequency value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
O.Total[1].Acceleration
Decimal
BOOL
Enables the Acceleration alarm on output connected to
channel 1. When the absolute acceleration exceeds the
Acceleration Alarm value, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
Table 15 - Configurable Flowmeter Module Output Tags
Name
Style
Data type
Definition