130 Software Configuration Tags
I.Status[0].FillState
Decimal
SINT
Displays current state of module for channel 0. The
following states are possible:
0 = Filler not active
1 = Filler Enabled only, waiting for start
2 = Timed Trickle Flow complete, not filled
3 = Full Flow for Fill function
4 = Timed Trickle Flow for Fill function
5 = Engineering units for Full Flow
6 = Engineering units for Trickle Flow
7 = Fill complete
I.Status[0].ConsumerErrorCode
Decimal
INT
I.Status[0].TotalCounts
Decimal
DINT
Displays actual pulses counted by the counter
connected to the channel 0
I.Status[0].FreqAverage
Float
REAL
Displays frequency averaged over the Meter samples
on channel 0
I.Status[0].FreqPeriod
Float
REAL
Displays frequency using sample time on channel 0
I.Status[0].Speed
Float
REAL
Displays frequency using filter resolution on channel 0
I.Status[0].Acceleration
Float
REAL
Displays acceleration on channel 0 as calculated by
using AccelCalculation samples
I.Status[0].FillTotal
Float
REAL
Fill total in engineering units
I.Status[0].GrossVolume
Float
REAL
Total Counts during each Sample/K-factor x Meter
Factor as occurs on channel 0
I.Status[0].NetVolume
Float
REAL
Total Counts during each Sample/K-factor x
MeterFactor x CCF) as occurs on channel 0
I.Status[0].GrossRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x Sample
Interval) x Meter Factor as occurs on channel 0
I.Status[0].NetRate
Float
REAL
Total Counts in Meter Sample/ (K-factor x Sample
Interval) x Meter Factor x CCF as occurs on channel 0
I.Status[0].ProverTotal
Float
REAL
Displays total counts (in engineering units) received on
channel 0 in prover operation.
Total resets when the ProverEnable feature is enabled.
This value operates concurrently with NetVolume, and
must be saved if subtracted from the NetVolume for
single and multiple prover verifications.
I.Status[1].ProverState
Decimal
SINT
Displays status of the prover operation on channel 1
0 = Prover Not Active
1 = Prover waiting for 1
st
start
2 = Prover waiting for 1
st
stop
3 = Prover waiting for 2
nd
start
4 = Prover waiting for 2
nd
stop
5 = Prover Complete
Table 14 - Configurable Flowmeter Module Input Tags
Name
Style
Data type
Definition