Rockwell Automation Publication 1756-UM010B-EN-P - December 2011
112 Configuring the Configurable Flowmeter Module
C.Ch0LowFreqClear
Decimal
BOOL
Enables the minimum detectable frequency
level for Channel 0.
Set the bit to 1 to enable it
1
C.Ch0PreTrigger
Decimal
BOOL
Enables the PreTrigger on Channel 0 for full
flow.
Set the bit to 1 to enable it
1
C.Operations[0].FillMode
Decimal
SINT
Sets the Trickle mode to complete on fill total
target or time.
0 = Fill total target (Engineering units)
1 = Time (seconds)
0
O.OutputControl[0].0
Decimal
BOOL
Manually sets the operation of outputs
connected to channel 0.
0 = Module operation of outputs
1 = Override Output0 to 0
2 = Override Output0 to 1
0
O.Total[0].FillEnable
Decimal
BOOL
Enables the filling operation on output
connected to channel 0.
0 = Fill operation is disabled
1 = Fill operation is enabled.
0
O.Total[0].FillStart
Decimal
BOOL
Begins filling operation when Fill Enable is
enabled on output connected to channel 0.
0 = Do not begin filling
1 = Begin filling
0
O.Total[0].FillHold
Decimal
BOOL
Holds/pauses filling operation on output
connected to channel 0
0 = Continue filling operation
1 = Hold/pause filling operation
0
O.Total[0].FillTotalTarget
Float
REAL
Target for Fill Complete, except when Fill
Transition is greater than this value.
100
O.Total[0].FillTransition
Float
REAL
When fill cycle is started, trickle flow is
initiated when the Fill Total is equal to or
greater than this value. Full flow is initiated
when the Fill Total is less than this value.
75
O.Total[0].FillTransitionTimer
Float
REAL
When timed trickle flow is selected, the
status remains ON for this time during this
state.
The value must be changed prior to entering
the trickle flow state.
1.0
O.Total[0].Overrange
Decimal
BOOL
Enables the Overrange alarm on output
connected to channel 0. When the Frequency
Period exceeds 100KHz, this alarm is set.
0 = No Alarm
1 = Alarm Enabled
0
Table 9 - Tag Changes Required for Totalizer Mode Using Filler Function
Name
Style
Data type
Definition
Enter
this
Value