Function Block Library

4–8

1336 FORCE — 5.9 August 1995

PARAMETERS

DATA TYPE

LINKABLE

DEFAULT VALUE

RANGE

In1

Signed Integer

Yes

0

±

32767

Pre

Signed Integer

No

0

±

32767

Hyst

Unsigned Integer

No

0

0 to + 32767

EQ

Logic Output

No

True/False

LT

Logic Output

No

True/False

GT

Logic Output

No

True/False

EXAMPLES

EXAMPLE 1

EXAMPLE 2

In1

8

15

Pre

10

10

Hyst

3

3

EQ

True

False

LT

True

False

GT

False

True

COMPHYST