background image

5–41

Block Transfer Services

1336 FORCE — 5.9 August 1995

The Read Node Value message reads the value of the specified
function block node.

PLC Block Transfer Instruction Data

BTW Instruction Length:

3 Words

BTR Instruction Length:

4 Words

Header

Word 1

PLC Hex Value

0F01

Message Structure

Header

Word 2

Header

Word 3

PLC Request –– Block Transfer Write

Header Word 1

Header Word 2

Header Word 3

0

Data

Word 4

0

PLC Hex Value

0F01 –– Message OK

8F01 –– Message Error

Node

Value

ID

N

8NID

High Byte

Low Byte

Drive Response –– Block Transfer Read

where:

N = the node number

ID = the block ID number

ID

N

8NID

High Byte

Low Byte

If N=16, 8NID becomes 90ID.

Message Operation

Word 3 specifies the function block node.

ID indicates the block ID number is specified in the low byte.

N indicates the node number is specified in the high byte (bits 8
through 14).

Example

In this example, a Read Node Value message was sent to the drive to
read the value of node 1 of the Scale function block (block ID 11

Dec

,

0B

Hex

). The drive response indicates the value of node 1 is 4.

1

0

N10:10

2

3

4

5

6

7

8

9

N10:90

BTW
Data File

BTR
Data File

Data Format

810B

810B

4

0

0

0F01

0F01

Note: The output of a Bin2Dec block is node 16

Dec

, and would be

specified as 900B if it were assigned a block ID number of 11

Dec

.

Node Adjustment:

Read Node Value

"