1–22

Getting Started

1336 FORCE — 5.9 August 1995

— Link Analog Output 1 to the Rate Limit Output

BTW
Data File

N57:0

4

8900

183

8504

0

0

0

0

0

0

0

1

2

3

4

5

6

7

8

9

1. Link Analog Output 1 (Parameter 387) to the Rate Limit output

(Block 4, Node 5).

2. Toggle bit I:00/00 to initiate the block transfer routine which

processes all function block links.

3. Verify that the write was successful. If N57:101 = 0900

hex

(Block

Transfer Read data), there are no errors.

— Link Analog Output 3 to the Rate Limit Input

BTW
Data File

N57:0

4

8900

185

8004

0

0

0

0

0

0

0

1

2

3

4

5

6

7

8

9

1. Link Analog Output 3 (Parameter 389) to the Rate Limit Input

(block 4, node 0).

2. Toggle bit I:00/00 to initiate the block transfer routine which

processes all function block links.

3. Verify that the write was successful. If N57:101 = 0900

hex

(Block

Transfer Read data), there are no errors.