Application control commands, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual
Page 135: Bram functions store, recall, and initialize

5–19
Block Transfer Services
1336 FORCE — 5.9 August 1995
The PLC Communication Board sends this message to activate the
function block BRAM function that is detailed in the message
request.
PLC Block Transfer Instruction Data
BTW Instruction Length:
4 Words
BTR Instruction Length:
4 Words
PLC Decimal Value
-28926
Not used
0
BRAM Command
BRAM Store
BRAM Recall
BRAM Initialize
BRAM Command
Value
0
1
2
3
Message Structure
PLC Request –– Block Transfer Write
Data Word 4
Header Word 1
Header Word 2
Header Word 3
Header
Word 1
PLC Decimal Value
3842 –– Message OK
0
–28926 –– Message Error
Header
Word 2
Header
Word 3
0
0
Drive Response –– Block Transfer Read
BRAM Command
Data
Word 4
Message Operation
A BRAM Store saves the function block program that is currently in
RAM to the function block BRAM/EEPROM.
A BRAM Recall copies the function block program that is stored in
BRAM to RAM. The drive executes the program stored in RAM.
A BRAM Initialize erases the function block program stored in
RAM and all associated function block links including links to linear
drive parameters. A BRAM Initialize function does not actually
clear out the BRAM itself; it only clears the function block
application out of the working RAM area.
Refer to Chapter 3 for a more detailed description of BRAM
functionality.
Application Control
Commands:
BRAM Functions
Store, Recall, and Initialize
"