beautypg.com

Rockwell Automation 1336T Function Block Prog. Manual, Series A/B User Manual

Page 48

background image

2–14

System Component Detail

1336 FORCE — 5.9 August 1995

If you are using a PLC, you would create this same link by doing the
following:

1. Set up your block transfer read and write blocks.

2. Create your data table. For this example, your data table would

look like the following:

BTW
Data File

N10:10

0

8F04

8002

8301

0

1

2

3

4

5

6

7

8

9

Write Link

Service

Request

Destination

Node

Source

Node

The 8002 in column 2 specifies that Node 0 of Block ID 2 (the
Set Reset FF function block) is receiving information. The 8301
specifies that Node 3 of Block ID 1 (the LIMIT function block) is
providing the information.

3. Perform a link processing service request.