Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 89
![background image](/manuals/578264/89/background.png)
Programming
5-21
Advanced Setup Group
(continued)
[Analog Invert]
Parameter # 84
Factory Default ‘‘Disabled”
[Analog Invert]
Parameter Type Read & Write
This parameter enables the inverting function for the 0-10
Volt and 4-20mA analog input signal at TB2.
Units Text
Settings ‘‘Enabled”
Maximum Input Commands [Minimum Freq]
Minimum Input Commands [Maximum Freq]
Volt and 4-20mA analog input signal at TB2.
‘‘Disabled”
Maximum Input Commands [Maximum Freq]
Minimum Input Commands [Minimum Freq]
Figure 5.12 Analog Invert
[Maximum Frequency]
'
0 V
4 mA
Drive Output
y
10 V
20 mA
y
[Minimum Frequency]
'
Disabled
Enabled
[4-20mA Loss Sel]
Parameter # 81
Factory Default ‘‘Stop/Fault”
[4 20mA Loss Sel]
Parameter Type Read & Write
This parameter selects the drives reaction to a loss of a
4 20 A i
l h
th
ti
[F
S
] i
Units Text
Settings ‘‘Stop/Fault”
Drive Stops and Issues ‘‘Hz Err Fault” (F29)
p
4-20mA signal when the active [Frequency Source] is
4 20mA Important: The drive output contacts can be
‘‘Hold/Alarm”
Drive Maintains Last Output Freq and sets an Alarm bit
4-20mA. Important: The drive output contacts can be
used to issue an alarm signal by setting [Output 1 Config]
‘‘Max/Alarm”
Drive Outputs [Maximum Freq] and sets Alarm bit
used to issue an alarm signal by setting [Output 1 Config]
or [Output 2 Config] to “alarm”. Important: Loss of signal
‘‘Pre1/Alarm”
Drive Outputs [Preset Freq 1] and sets an Alarm bit
or [Output 2 Config] to alarm . Important: Loss of signal
is defined as a signal < 3.5 mA or a signal > 20.5 mA.
‘‘Min/Alarm”
Drive Outputs [Minimum Freq] and sets an Alarm bit