Installation/Wiring
2-11
POWER WIRING
Input and output power connections are performed through a
ten position terminal block, TB1 (see page 2-3 for location).
Figure 2.6 Power Terminal Block Designations (TB1)
➀ Connection for Dynamic Brake Resistors for all models except the 200-230 Volt,
0.37 to 0.75 kW (0.5 to 1 HP) drive. Important: The [DB Enable] parameter must
be enabled for proper operation.
➁ For single phase applications, the AC input line can be connected to any two of
the three input terminals R, S, T (L1, L2, L3).
➂ 1305 drives are UL and cUL listed, and CSA certified as a motor overload
protective device. An external overload relay is not required for single motor
applications. Important: This drive is not intended for use with single phase
motors.
➃ Ground from drive to motor frame must be an independent continuous insulated
wire run.
GRD
To Motor
➃
Required
Input Fusing
L1
R
L2
S
L3
T
+DC
BRK ➀
(–DC)
T1
U
T2
V
T3
W
AC Input Line
➁
To Motor
➂
Dynamic Brake
Option
Required Branch
Circuit Disconnect
GRD
Table 2.B Power Block Terminal (TB1)
Terminals
Description
GRD
Earth Ground
R, S, T (L1, L2, L3)
AC Input Line Terminals
+DC, BRK (or –DC)
Dynamic Brake Option - Refer to instructions in-
cluded with option
U, V, W (T1, T2, T3)
Motor Connection
Table 2.C Screw Size, Wire Size and Torque Specifications
Terminal
Screw
Size
Max./Min. Wire Size
mm
2
(AWG
)
Maximum Torque
N-m ( lb-ins. )
TB1 (0.37-0.75 kW/0.5-1 HP)
M4
3.5/0.75 (12/18)
0.90 (8)
TB1 (All except above)
M4
4/0.75 (10/18)
1.81 (16)
TB2 (All)
M3.5
1.5/0.20 (14/24)
0.90 (8)