Programming

5-45

Diagnostics Group

(continued)

[Freq Source]

Parameter # 62

[Freq Source]

Parameter Type Read

This parameter displays the frequency source currently
commanding the drive.

Units Text

Displays ‘‘Remote Pot”

‘‘0-10 Volt”
‘‘4–20 mA”
‘‘MOP”
‘‘Adapter 1”
‘‘Adapter 2”
‘‘Adapter 3”
‘‘Adapter 4”
‘‘Adapter 5”
‘‘Adapter 6”

‘‘Preset 1”
‘‘Preset 2”
‘‘Preset 3”
‘‘Preset 4”
‘‘Preset 5’’
‘‘Preset 6”
‘‘Preset 7”

[Freq Command]

Parameter # 65

Factory Default 0.00 Hz

[Freq Command]

Parameter Type Read Only

Minimum 0.00 Hz

This parameter displays the frequency that the drive is
commanded to output. This command may come from any
one of the frequency sources selected by [Freq Select 1],
[Freq Select 2] or [Preset Freq 1-7] as determined by
inputs to SW1, SW2 and SW3 at TB2.

Units 0.01 Hz

Maximum 400.00 Hz

[Drive Direction]

Parameter # 69

Factory Default ‘‘Forward’’

[Drive Direction]

Parameter Type Read Only

This parameter displays the running direction of the drive.

Units Text

Displays ‘‘Forward”

‘‘Reverse”

[Motor Mode]

Parameter # 43

[Motor Mode]

Parameter Type Read Only

This parameter is used for internal diagnostic purposes.