Human Interface Module

3-15

CONTROL STATUS MODE

ACTION

DESCRIPTION

HIM DISPLAY

Control Logic

or

or

or

SEL

❏ 1. The Control Status mode is only available with Series A HIM software

version 3.00 and above or Series B HIM software version 1.01 and above.

This mode allows the drive logic mask to be disabled, thus preventing a
Serial Fault when the HIM is removed with drive power applied.

a. From the Status Display, press Enter (or any key). “Choose Mode” will

be shown.

b. Press the Increment (or Decrement) key until “Control Status” is

displayed. Press Enter.

c. Select “Control Logic” using the Increment/Decrement keys. Press

Enter.

d. Press the SEL key, then use the Increment (or Decrement) key to select

“Disabled” (or “Enable”).

e. Press Enter. The logic mask is now disabled (or enabled).

Choose Mode
Display

Choose Mode
Control Status

Control Status
Control Logic

Control Logic
Disabled