Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 160
Drive Accessories
C-2
Table C.2 Accessories
Accessory
Specifications
Line Reactor
Iron core, 3% Impedance, 600V, Class H insulation, 115
_C rise,
copper wound, 50/60 Hz, terminal blocks, UL, CSA
Isolation
Transformer
230V/230V or 460V/460V, Delta primary/Wye secondary, Class H
insulation, 150
_C rise, aluminum wound, 60 Hz, "5% taps, (1)
N.C. thermostat per coil, UL, CSA
Terminators
NEMA 4, 460V units – Refer to “Motor Lead Lengths” for proper
selection.
Drive Out.
Ratings
Input Line Reactors
Isolation
Transformer
Terminators
HP
kW
Open Style
NEMA Type 1
NEMA Type 1
NEMA Type 4
230V AC
0.5
0.75
1
2
3
0.37
0.55
0.75
1.5
2.2
1321-3R4-B
1321-3R4-A
1321-3R4-A
1321-3R8-A
1321-3R12-A
1321-3RA4-B
1321-3RA4-A
1321-3RA4-A
1321-3RA8-A
1321-3RA12-A
1321-3T003-AA
1321-3T003-AA
1321-3T005-AA
1321-3T005-AA
1321-3T005-AA
––
––
––
––
––
460V AC
0.5
0.75
1
2
3
➀
3
5
➀
5
0.37
0.55
0.75
1.5
2.2
2.2
4.0
4.0
1321-3R2-B
1321-3R2-A
1321-3R2-A
1321-3R4-B
1321-3R4-B
1321-3R8-B
1321-3R8-B
1321-3R12-B
1321-3RA2-B
1321-3RA2-A
1321-3RA2-A
1321-3RA4-B
1321-3RA4-B
1321-3RA8-B
1321-3RA8-B
1321-3RA12-B
1321-3T003-BB
1321-3T003-BB
1321-3T005-BB
1321-3T005-BB
1321-3T005-BB
1321-3T005-BB
1321-3T005-BB
1321-3T007-BB
––
––
1204-TFA1
1204-TFA1 or TFB2
1204-TFA1 or TFB2
1204-TFA1 or TFB2
1204-TFA1 or TFB2
1204-TFA1
Drive Output Ratings
Dynamic Brake Kits
➁
HP
kW
Dynamic Brake Kits
➁
(Kits must not be wired in parallel)
230V AC
0.5-1
2-3
0.37-0.75
1.5-2.2
Not Required
1305-KAA12
460V AC
0.5-1
2-3
5
0.37-0.75
1.5-2.2
4.0
1305-KBA03
1305-KBA06
1305-KBA09
➂
CE Conformance
Filters
RFI Filters, Kits, and Metal Conduit
Plates Required to Meet CE Directives
Filter (RFB)
Metal Plate Kit (MP)
0.5 – 0.75 HP (230V)
1305-RFB-05-A
1305-MP-05-A
(
)
1 HP (230V)
1305-RFB-05-A
1305-MP-06-A
2 HP (230V), 0.5 – 3 HP (460V)
1305-RFB-08-B
1305-MP-08-B
3 HP (230V), 5 HP (460V)
1305-RFB-12-C
1305-MP-12-C
Note: Spare plastic parts are available – contact factory.
➀ Input reactor only.
➁ [DB Enable] should be set to ‘‘Enable” when applying external dynamic brake kits.
➂ For use with Series C or B Drives only. DO NOT use with Series A Drives.