Advanced setup group – Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual

Page 87

background image

Programming

5-19

Advanced Setup Group

(continued)

[Start Boost]

Parameter # 48

Factory Default See Table

0.37 kW
(0.5 HP)

0.55 kW
(0.75 HP)

0.75 kW
(1 HP)

1.5 kW
(2 HP)

2.2 kW
(3 HP)

4.0 kW
(5 HP)

Parameter Type Read & Write

Minimum 0 Volts

230V

3 Volts

3 Volts

3 Volts

3 Volts

3 Volts

N/A

This parameter sets the DC boost level for

l

ti

h

[DC B

t S l t] i

t t ‘‘R

Units 1 Volt

Maximum 25% of

M

D i

460V

12 Volts

12 Volts

12 Volts

9 Volts

6 Volts

6 Volts

p

acceleration when [DC Boost Select] is set to ‘‘Run
Boost” or ‘‘Break Point.”

Max. Drive
Rated Volts

Figure 5.10 Start/Run Boost

[Base Voltage]
[Base Frequency]

b

0 –

0

Voltage

Frequency

[Start Boost]

'

[Run Boost]

'

Active when [DC Boost Select] is set to ‘‘Run Boost”

a

150% of Start Boost

a

150% of Run Boost

[Run Boost]

Parameter # 83

Factory Default 0 Volts

[Run Boost]

Parameter Type Read & Write

Minimum 0 Volts

This parameter sets the DC boost level for constant speed
level when [DC Boost Select] is set to ‘‘Run Boost.” [Run
Boost]
must be set at a value less than [Start Boost].

Units 1 Volt

Maximum 25% of Max. Drive Rated Volts