Programming

5-15

This group contains parameters that are required to setup advanced functions of the drive such as custom
Volts per Hertz settings and dynamic braking.

Advanced

Setup

[Minimum Freq]

Parameter # 16

Factory Default 0 Hz

[Minimum Freq]

Parameter Type Read & Write

Minimum 0 Hz

This parameter sets the lowest frequency the drive will
output.

Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq].

Units 1 Hz

Maximum 120 Hz

Important: This parameter can not be
programmed while the drive is running.

[Maximum Freq]

Parameter # 19

Factory Default 60 Hz

[Maximum Freq]

Parameter Type Read & Write

Minimum 40 Hz

This parameter sets the highest frequency the drive will
output.

Important: All analog inputs to the drive (4-20mA, 0-10V,
Remote Pot) are scaled for the range [Minimum Freq] to
[Maximum Freq]

Units 1 Hz

Maximum 400 Hz

Important: This parameter can not be
programmed while the drive is running.

[Base Frequency]

Parameter # 17

Factory Default 60 Hz

[Base Frequency]

Parameter Type Read & Write

Minimum 40 Hz

This value should be set to the motor nameplate Rated
Frequency.

Units 1 Hz

Maximum 400 Hz