Programming
5-32
This group contains the necessary parameters to activate and program advanced features of the drive.
Feature
Select
[Run On Power Up]
Parameter # 14
Factory Default ‘‘Disabled”
[Run On Power Up]
Parameter Type Read & Write
This parameter enables the function that allows the drive to
automatically restart on power up regardless of what the
Units Text
Settings ‘‘Enabled”
‘‘Disabled”
automatically restart on power up regardless of what the
drive status was before power is lost. This applies only
when there is a maintained input to the start and stop
inputs. Refer to Chapter 2, Figure 2.7 through Figure 2.10.
ATTENTION: This parameter may only be used as
outlined in NFPA 79, paragraph 6-14 (exceptions 1-3)
for specialized applications. Equipment damage
and/or personal injury may result if this parameter is
used in an inappropriate application.
!
[Reset/Run Tries]
Parameter # 85
Factory Default 0
[Reset/Run Tries]
Parameter Type Read & Write
Minimum 0
This value sets the maximum number of times the drive
attempts to reset a fault and restart before the drive issues
a ‘‘Max Retries Fault.” Not operative for faults 9, 10, 11,
24, 25, 26, 29, 30, 32, 33, 34, 35, 38, 39, 40, 41, 42,
43 and 48.
Important: [Reset/Run Tries] is a cumulative count. This
counter resets to zero if four (4) minutes elapses since the
last fault.
Units Numeric
Maximum 9