Rockwell Automation 1305 AC Drive, Series C, Firmware 6.xx and Up User Manual
Page 30

Installation/Wiring
2-16
Table 2.E Maximum Motor Cable Length
Reactor
➀
at the Drive
With 1204-TFB2 Terminator
With 1204-TFA1 Terminator
Using a Motor with Insulation V
P-P
Using a Motor with Insulation V
P-P
Using a Motor with Insulation V
P-P
Drive HP
Motor HP
1000 Volt
1200 Volt or 1600 Volt
Using a Motor with Insulation V
P-P
1000 Volt or 1200 Volt
1000 Volt
1200 Volt
Drive HP
(460V)
Motor HP
(460V)
Any Cable
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Shielded
Unshielded
Maximum Carrier Frequency
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
2 kHz
High-Line Derating Multiplier
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
0.85
5
5
15m (50ft)
182m (600ft)
182m (600ft)
NR
NR
91m (300ft)
61m (200ft)
91m (300ft)
121m (400ft)
3
15m (50ft)
182m (600ft)
182m (600ft)
91m (300ft)
121m (400ft)
99m (325ft)
61m (200ft)
152m (500ft)
121m (400ft)
2
15m (50ft)
182m (600ft)
182m (600ft)
121m (400ft)
182m (600ft)
99m (325ft)
61m (200ft)
182m (600ft)
121m (400ft)
3
3
15m (50ft)
91m (300ft)
182m (600ft)
NR
NR
91m (300ft)
61m (200ft)
91m (300ft)
121m (400ft)
2
15m (50ft)
182m (600ft)
182m (600ft)
91m (300ft)
121m (400ft)
99m (325ft)
61m (200ft)
152m (500ft)
121m (400ft)
1
15m (50ft)
182m (600ft)
182m (600ft)
91m (300ft)
182m (600ft)
99m (325ft)
61m (200ft)
182m (600ft)
121m (400ft)
2
2
15m (50ft)
76m (250ft)
167m (550ft)
NR
NR
91m (300ft)
61m (200ft)
91m (300ft)
121m (400ft)
1
15m (50ft)
182m (600ft)
182m (600ft)
61m (200ft)
61m (200ft)
99m (325ft)
61m (200ft)
121m (400ft)
121m (400ft)
0.5
15m (50ft)
182m (600ft)
182m (600ft)
91m (300ft)
121m (400ft)
99m (325ft)
61m (200ft)
152m (500ft)
121m (400ft)
1
1
15m (50ft)
68m (225ft)
152m (500ft)
NR
NR
45m (150ft)
61m (200ft)
45m (150ft)
76m (250ft)
0.5
15m (50ft)
121m (400ft)
182m (600ft)
NR
NR
76m (250ft)
61m (200ft)
76m (250ft)
121m (400ft)
0.5
0.5
15m (50ft)
45m (150ft)
106m (350ft)
NR
NR
NR
NR
NR
NR
NR = Not Recommended.
➀ Important: A 3% reactor reduces motor stress but may cause a degradation of motor waveform quality. Reactors must have a turn-to-turn insulating rating of 2100 volts or higher.
Reactors are not recommended for lightly loaded applications because overvoltage trips may result at low output frequencies.