Safety Outputs
Chapter 11
Jog
The Jog block turns on the output for a specified duration while the jog input is
held HI. If the Jog input goes LO, the output immediately turns off.
shows the Jog output block that is connected to an enabling switch
block through Logic Level LLB1. The reset is set to automatic. The time delay is
set to 40. The output will turn on for a maximum of 2000 ms (40x50 ms) after
the enabling switch is closed. The output is connected to:
•
Terminals 18 and 19 for dual channel safety switching of the machine
hazards.
•
Terminal 20, which is configured as a Single Wire Safety (SWS) output.
•
Plug-in 1 terminal 03 for status indication.
Figure 104 - Jog Configuration
Muting Lamp
The Muting Lamp block works with the Muting safety monitoring function.
The muting lamp is not monitored. If the lamp burns out or becomes
disconnected, the muting function continues to function properly.
shows the muting lamp output block connected to the mute function
in SMF1. The output is connected to:
•
Terminal 14, a multi-purpose terminal with no pulse testing (No PT).
•
Plug-in 1 terminal 00 for more status indication.
•
The muting lamp should be connected to terminals without pulse testing.
Pulse testing does not affect filament lamps, but LED lamps can appear to
flicker if pulse testing is enabled.
Figure 105 - Muting Lamp Configuration