Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual

Page 131

background image

Rockwell Automation Publication 440C-UM001C-EN-P - November 2014

131

Specifications

Appendix A

The overall monitoring time to evaluate a fault and initiate a system response,
after the occurrence of a recoverable fault must consider any specific-fault
processing times depending on the I/O evaluation method and configured input
filter times.

Table 26

shows the response time for specific recoverable faults, if the

safety function is not demanded, and the required settings of SMF and SOF to
enable the proper fault evaluation method.

Table 26 - Processing Time of Recoverable Faults and Required Settings

Table 27 - Response time of the Safety Chain at Occurrence of Recoverable Faults without a
Demand of the Safety Function

Recoverable Fault

Detection Enabled by

Processing Time

Cross loop fault

Inputs: 2 N.C.
Pulse Testing: 2 Sources

3 s

Short circuit fault

Inputs: 1 N.C., or 2 N.C.
Pulse Testing: 1 Source, 2 Sources

3 s

Input discrepancy fault

Inputs: 2 N.C., 2 OSSD
Discrepancy Time: >0…3 s

Discrepancy time + Input Filter time

Reset/restart timing fault

Default: 0.25…3 s

0 s

(1)

(1) A Reset/Restart Timing Fault can only occur when safety outputs are OFF, so there is no impact on the safety response time

Non-retriggerable timer fault

Retriggerable: Disabled

Configured time delay

(2)

(2) The maximum of the configured delay must be considered. The remaining time at occurrence of fault will lapse.

Muting: Synchronization time
exceeded

Synch Time: 0.05…10 s
Muting Sensors Input Filter: 0…3 s

Max. Synch Time

(3)

+ 2 x Input Filter Time

(3) The synchronization time between the Muting Sensors, and between Muting Sensor can be set individually. The longest

synchronization must be considered.

Muting time exceeded

Max. Mute Time: 1 s…10 days

Configured Max. Mute Time

Muting sequence fault

Muting Type: 2 Sensor T-Type, 2
Sensor L-Type, 4 Sensor

Input Filter Time

Description

Where to find:

Value

SMF

Fault processing

Above table, according to
configured input
evaluation of the SMF

Logic

Internal execution time to
process input signal,
routing and output
processing

(1)

(1) The internal execution time is static and independent of the number of function blocks that are configured for the safety function.

From technical
specification

45 ms (fix)

SOF

Fault processing time and
configured time delay

From SOF configuration

Actuator

Safety switching device
controlling the load

Actuator Operating manual

Total