Chapter
17
Using the Memory Module
Overview
Guardmaster 440C safety relays support the Cat. No. 2080-MEMBAK-RTC
memory modules for the following purposes:
•
Project backup and restore
•
Firmware and project backup and restore
Project Backup and Restore
Project backup and restore on Guardmaster 440C safety relays are supported
through the Cat. No. 2080-MEMBAK-RTC memory module. Both backup and
restore can be initiated through the Connected Components Workbench™
(CCW) software and using buttons physically present on the Guardmaster 440C
safety relay and the Cat. No. 2080-MEMBAK-RTC module.
A backup of both the Guardmaster 440C safety relay firmware and project can
only occur through the CCW software.
ATTENTION: Removal and Insertion Under Power (RIUP) is not supported on
the Cat. No. 2080-MEMBAK-RTC memory module when used with a
Guardmaster® 440C safety relay.
ATTENTION: The Cat. No. 2080-MEMBAK-RTC module can only be installed in
Slot 1 (the leftmost plug-in slot) on the Guardmaster 440C safety relay.
IMPORTANT
Do not remove the Cat. No. 2080-MEMBAK-RTC or power down while
operations such as backup and restore are ongoing to prevent data loss. A
blinking status indicator on the memory module indicates that these
operations are ongoing.
IMPORTANT
Backup can only occur when the safety relay is in the Safety Verified state. To
learn about safety verification, see
IMPORTANT
Using the Cat. No. 2080-MEMBAK-RTC with the CR30 is only supported with
firmware revision 7 or later.