Wire size, Terminal assignments, Wire size terminal assignments – Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 20
20
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Chapter 3
Power, Ground, and Wiring
Wire Size
Table 1 - Wiring Requirements
Terminal Assignments
Some terminals are designed to have one specific function. Some terminals can
perform multiple functions; these terminals must be configured in the
application software.
Table 2 - Terminal Assignments
Wire Size
Type
Min
Max
Copper
Stranded
0.326 mm
2
(22 AWG)
1.31 mm
2
(16 AWG)
Rated @ 90 °C (194 °F)
insulation min.
Terminal
Function
00
Safety Input (N.C.)
01
Safety Input (N.C.)
02
Safety Input (N.C.)
03
Safety Input (N.C.)
04
Safety Input (N.C.)
05
Safety Input (N.C.)
06
Safety Input (N.C.)
07
Safety Input (N.C.)
08
Safety Input (N.C.)
09
Safety Input (N.C.)
10
Safety Input (N.C.) or Single Wire Safety Input
11
Safety Input (N.C.) or Single Wire Safety Input
+24V DC
A1 Power Supply (+24V, -15%, +10%)
COM 0V
A2 Power Supply (0V)
12
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
13
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
14
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
15
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
16
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
17
Test Output or OSSD High Side or Safety Input (N.C.) or Safety Input N.O. or standard diagnostic.
18
OSSD High Side
19
OSSD High Side
20
OSSD High Side or Single-wire Safety Output
21
OSSD High Side or Single-wire Safety Output