Specifications
Appendix A
Response Time - Demand of the Safety Function
The safety response time of CR30 is the screw-to-screw response time to turn off
a safety output at demand of the safety function by the safety input device. The
safety response has to be calculated for each safety monitoring function.
shows the possible safety chain with all considerable response times.
Table 21 - Safety Chain Response Times
shows the additional processing time of dedicated SMF
Table 22 - Processing Time
Description
Where to find:
Value
Safety Sensors
Safety response time of sensor device
Sensor operating manual
SMF
Specific Processing time of safety
monitoring function configured in CCW
Below table of specific SMF processing
times
Input Filter
Configured Input Filter time
From SMF configuration “advanced
settings”
(2)
(2) The maximum input filter time shall not be greater than 250 ms.
Logic
Internal execution time to process input
signal, routing and output processing
(1)
(1) The internal execution time is static and independent of the number of function blocks that are configured for the safety function.
From technical specification
45 ms
SOF
Configured Off-Delay time
From SOF configuration
Actuator
Safety switching device controlling the
load
Actuator operating manual
Total
SMF
Description
SMF response time
Emergency Stop
SMF inputs deactivated
0 ms
Enabling Switch
Gate Switch
Light Curtain
Alternative Device
Muting
N/A
0 ms
Light Curtain
Light interrupted, not muted
0 ms
Override
Deactivate Override when light
curtain is interrupted
0 ms
Safety Mats
Step on Mat, cross loop between
safety mat inputs
25 ms
Single Wire Safety
Deactivated SWS signal
15 ms
Two Hand Control
Release of at least 1 Hand actuator
0 ms