Rockwell Automation 440C Guardmaster 440C-CR30 Configurable Safety Relay User Manual User Manual
Page 128

128
Rockwell Automation Publication 440C-UM001C-EN-P - November 2014
Appendix A
Specifications
The evaluation method of the input or output signal depends on the
configuration of the SMF and SOF in CCW and the wiring of the sensor.
shows typical evaluation functions and required settings to be enabled.
Table 25 - Evaluation Method
Evaluation Method
Configuration
Applicable for
Multi-channel signal evaluation
Inputs: 2 N.C., 2 OSSD, 3 N.C.
(1)
or
3 OSSD
SMF:
Emergency Stop
Enabling Switch
Gate Switch
Light Curtain
Two Hand Control
Alternative Device
Muting: Light Curtain settings
Muting: Override settings
Test pulse evaluation
Test Pulses: 1 or 2 sources, or 3
sources
: >0
SMF:
Emergency Stop
Enabling Switch
Gate Switch
Two Hand Control
Alternative Device
Muting: Override settings
Input Discrepancy Time
Discrepancy Time
(2)
: >0
Range: 0.05…3 s
SMF:
Emergency Stop
Enabling Switch
Gate Switch
Light Curtain
Two Hand Control
Alternative Device
Muting: Light Curtain settings
Muting: Override settings
Two Hand Discrepancy Monitoring
Default: 0.5 s
The maximum amount of time
between activation of Hand 1 and
Hand 2 to enable SMF
SMF
Two Hand Control
Muting Sequence
Muting Type: 2 Sensor T-Type, 2
Sensor L-Type, 4 Sensor
Defines the type of muting
application and thus the valid
sequence of clearing or blocking the
muting sensors and protective
device.
SMF
Muting