Installation/Wiring

1-33

Table 1.M Fiber Optic Cable Assembly

Active Converter
Communication

The active converter communicates control and starts information with the
700S controller over DPI Data Link D.

• 700AC Parameter 71 - [Converter Status] is transferred to 700S

Parameter 657 - [DPI Data In D1]. This may be used to monitor the
operation of the active converter.

• 700S Parameter 666 - [DPI Data Out D1] is transferred to 700AC

Parameter 70 - [Converter Control]. This may be used to start and stop
the converter.

• 700S Parameter 667 - [DPI Data Out D2] is transferred to 700AC

Parameter 72 - [Converter Min Vdc]. This may be used to set the
minimum DC link voltage reference.

For more information, please refer to the PowerFlex 700 Active Converter
Power Module User Manual
(Publication No. PFLEX-UM002…).

Auto Tune Operation

The pre-charge bypass contactor must be closed and the converter must be
enabled before Auto Tuning of the inverter can be performed. See the
section below on Pre-charge Operation to accomplish this.

700S Parameter 431 sets the current level for the Auto Tune procedure. The
default value of 50.0% is high for large horsepower drives. A typical value
for a motor connected to an LPM20 drive is 20.0%.

After the converter is ready and parameters are set correctly, the Auto Tune
operation can be initiated from the HIM as described in the PowerFlex 700S
High Performance AC Drive — Phase II Control User Manual
(Publication
No. 20D-UM006…).

SynchLink Fiber-Hub, 1 input, Base

1751-SLBA

SynchLink Fiber-Hub, 4 output, “Star” Splitter

1751-SL4SP

SynchLink Bypass Switch

1751-SLBP/A

Specification
Connecting Cables

200/230 micron HCS (Hard Clad Silica)

• Versalink V-System

• Lucent Technologies,

• Specialty Fibers Technology Division

Maximum Cable Length

300 meters with no more than one splice or one adapter

Minimum Cable Length

1 meter

Minimum inside bend radius

25.4mm (1 in.) Any bends with a shorter inside radius can
permanently damage the fiber optic cable. Signal attention
increases with decreased inside bend radius.

Operating Wavelength

650 nm (Red)

Data Rate

5 Mbps

Maximum Node Count

• 10 - Daisy Chain

• 256 - Star Configuration

Table 1.L SynchLink Cables and Accessories (Continued)

Description Cat.

No.