beautypg.com

Figure 1.6 – Rockwell Automation LPM20 Liquid-Cooled AC Drive with High Performance Drive Control User Manual

Page 22

background image

1-10

Installation/Wiring

Figure 1.6 Drive Input Dimensions

Verifying that Site Provides for Recommended Air Flow Clearances

Be sure there is adequate clearance for air circulation around the
user-supplied enclosure. A 6-inch minimum clearance is required wherever
vents are located in the cabinet.

For proper cabinet ventilation, roof spacers must be field installed as shown
in

Figure 1.6

.

81.11

[2060]

20.157

[512]

Area for Input Power Wiring

23.80

[605]

26.20

[665]

23.82

[605]

2.38

[60]

6.076

[154,3]

Left Panel/Divider Panel

Edge Guard

Field Install
Roof Spacers
Rittal p/n
DK7967.000

Exhaust Air
Space Required

Divider Panel
Rittal p/n
TS8609.060

Area for Input Power Wiring

10.49

[266]

58.48

[1485]

80.89

[2055]

78.99

[2006]

10.13

[257]

Ref

12.24

[311]

Left View Shown

with Lifting Eye-Bolts

as Shipped

C/B

Disconnect

Handle

Rittal TS8 Enclosure

600mm x 600mm x 2000mm

Power Cable

Opening Input

to Power Module

Intake Louver

323mm x 323mm

Control Cable
Opening Input
to Power Module