1-8

Installation/Wiring

Figure 1.5 Power Module Dimensions and Mounting

2.65 From Back of

Chassis to ORFS of

Sealing Surfaces

21.97

6.66

20.66

4.48

4.48

4.48

6.75

1.43

1.50

0.88

0.75

Ø.472

0.25

2.31

4.75

Lifting
Ø1.00
Both Sides

18.49

3.05

16.00

Lifting Ø1.00 Both Sides

0.80

3.88

1.56

36.04

1.92

1.19

Ø.213 Thru
For M6 TAPTITE
Screw with Enclosure
Mounting Bracket

0.50

9.25

4.76

3.64

4.81

1.75

6.84

6.05

8.96

13.72

1.25

1.98

9.03

2.08

SEE DETAIL A

FRONT
VIEW

Drive

Output

Wiring

to Motor

Drive

Input

Wiring

W

V

U

L3

L2

L1

IN

OUT

LEFT SIDE VIEW

Coolant Connections
See Notes 2 and 3

A1-P1
Input Filter
Harness
Connector

DETAIL A

Input and Output Wiring Connection
SCALE 1:2

NOTES:
1. Floor Mounting Flange Holes:
A. Accept M8 Thread-Rolling Screws per SAE J1237.
B. Tightening Torque: 20-24 [N-M], 15-17 [FT-LBF].
2. Inlet and Outlet Coolant Connection Hardware Provided With Unit:
A. ORFS Braze Sleeve:
a. Material: Brass; for 5/8" O.D. Copper Tube.
b. Reference: Parker Hannifin P/N 10 TL-B, or equivalent.
B. ORFS Nut:
a. Material: Brass; for 5/8" O.D. Copper Tube, 1-14 UN/UNF-2B Thread.
b. Tightening Torque: 37-45 [N-M], 27.1-33.3 [FT-LBF].
c. Reference: Parker Hannifin P/N 10 BL-B, or equivalent.
3. Coolant Connection Hardware Provided by User:
A. ORFS Braze Adapter:
a. Material: Brass; for 5/8" O.D. Copper Tube, 1-14 UN/UNF-2A Thread.
b. Reference: Parker Hannifin P/N 10 LHB3-B, or equivalent.
B. ORFS O-Ring:
a. Material: Neoprene Rubber.
b. Size: 0.614 I.D., 0.070 Width.
c. Reference: Parker Hannifin P/N 2-016-C0873-70, or equivalent.
C. O-Ring Lubricant: Parker Hannifin Super-O-Lube, or equivalent.