Configuring the rs-485 network, Configuring the rs-485 network -5 – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 77

Using Multi-Drive Mode
7-5
The following parameters must be set in the daisy-chained drives:
Note that the RS-485 network is fixed at 19.2K baud, 8 data bits, no
parity, and 1 stop bit.
Important: Parameters A105 - [Comm Loss Action] and A106 -
[Comm Loss Time] in the daisy-chained drives are not
used in Multi-Drive mode. If the RS-485 cable is
disconnected or broken, the disconnected drive(s) will fault.
On the DeviceNet side, Parameters 07 - [Comm Flt
Action] and 08 - [Idle Flt Action] in the 22-COMM-D
determine the action taken for ALL of the drives on the
Multi-Drive node.
The following Multi-Drive parameters must be set in the 22-COMM-D:
After setting the 22-COMM-D parameters, set the adapter Mode Jumper
from Single drive operation to Multi-Drive operation, and reset the
adapter or cycle power. Refer to
Important: 22-COMM-D parameters can be set using a DSI peripheral
(HIM, DriveExplorer with 22-SCM-232, etc.) ONLY when
the Mode Jumper is in the Single mode position.
Configuring the RS-485 Network
Parameter
Value
P36 - [Start Source]
5 (“RS485 [DSI] Port”)
P38 - [Speed Reference]
5 (“RS485 [DSI] Port”)
A103 - [Comm Data Rate]
4 (“19.2K”)
A104 - [Comm Node Addr]
1-247 (must be unique)
A107 - [Comm Format]
0 (“RTU 8-N-1”)
Parameter
Value
15 - [DSI I/O Cfg]
00010 = Drives 0-1 connected
00100 = Drives 0-2 connected
01000 = Drives 0-3 connected
10000 = Drives 0-4 connected
17 - [Drv 0 Addr]
= Parameter A104 - [Comm Node Address] in Drive 0
18 - [Drv 1 Addr]
= Parameter A104 - [Comm Node Address] in Drive 1
19 - [Drv 2 Addr]
= Parameter A104 - [Comm Node Address] in Drive 2
20 - [Drv 3 Addr]
= Parameter A104 - [Comm Node Address] in Drive 3
21 - [Drv 4 Addr]
= Parameter A104 - [Comm Node Address] in Drive 4