Setting the node address, Setting the data rate – Rockwell Automation 22-COMM-D DeviceNet Adapter User Manual
Page 31

Configuring the Adapter
3-7
The value of Parameter 02 - [DN Addr Cfg] determines the node
address if all of the adapter DIP switches are in the CLOSED position
(all 0’s). We recommend that you do not use node address 63 because all
new devices use it as the default address. Address 63 is also used for
Automatic Device Recovery (ADR).
1. Set the value of Parameter 02 - [DN Addr Cfg] to a unique node
address.
Figure 3.5 DeviceNet Node Address Screen on PowerFlex 4-Class HIM (22-HIM-*)
2. Reset the adapter. Refer to
section in this chapter.
The value of Parameter 04 - [DN Rate Cfg] determines the DeviceNet
data rate if all of the adapter DIP switches are in the CLOSED position
(all 0’s). The Autobaud setting will detect the data rate used on the
network if another device is setting the data rate. Your application may
require a different setting.
1. Set the value of Parameter 04 - [DN Rate Cfg] to the data rate at
which your network is operating.
Figure 3.6 DeviceNet Data Rate Screen on PowerFlex 4-Class HIM (22-HIM-*)
2. Reset the adapter. Refer to
section in this chapter.
Setting the Node Address
DN Addr Cfg
Parameter:
#
002
63
VALUE
LIMITS
SEL
!
Default = 63
TIP: If you are using RSNetWorx for DeviceNet, select Network >
Single Browse Path to see the new address; then delete the old address.
Setting the Data Rate
Value Baud Rate
0
125 kbps
1
250 kbps
2
500 kbps
3
Autobaud (Default)
DN Rate Cfg
Parameter:
#
004
Autobaud
3
VALUE
LIMITS
SEL
!