Plc-5 controller example, Plc-5 controller example -9 – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual
Page 67
Using Block Transfer Messaging
5-9
20-COMM-R Remote Adapter I/O User Manual
Publication 20COMM-UM004D-EN-P
PLC-5 Controller Example
Block Transfer Data Files for PLC-5 Example Program
The following set of data files shows a read of drive parameter 1 - [Output
Freq]. The value of parameter 1 is 213 (21.3 Hz).
Request Data (BTW) to Read Drive Parameter 1 (Hex)
Response Data (BTR) to Read Drive Parameter 1 (Hex)
The following set of data files shows a write of drive parameter 41 - [Motor
NP Volts]. The value written is 2300 (230.0V AC).
Request Data (BTW) to Write to Drive Parameter 41 (Hex)
Response Data (BTR) to Write to Drive Parameter 41 (Hex)
See
Formatting Block Transfer Messages on page 5-2
for more information
on block transfer messages.
Address
Value (hex)
Description
See Page
N12:0
000A
Length of Message = 10 bytes (A hex)
N12:1
0081
Required Setting
N12:2
000E
Service = Get_Attribute_Single
N12:3
0093
Class = 93 DPI Parameter Object
N12:4
0001
Instance = Parameter 1 (1 hex)
N12:5
0009
Attribute = 09 DPI Parameter Value
Address
Value (hex)
Description
See Page
N13:0
0004
Length of Message = 4 bytes
N13:1
0000
The Message was Successful
N13:2
0000
N13:3
00D5
Response Data = 213 (D5 hex) = 21.3 Hz.
n/a
Address
Value (hex)
Description
See Page
N12:0
000C
Length of Message = 12 bytes (C hex)
N12:1
0081
Required Setting
N12:2
0010
Service = Set_Attribute_Single
N12:3
0093
Class = 93 DPI Parameter Object
N12:4
0029
Instance = Parameter 41 (29 hex)
N12:5
0009
Attribute = 09 DPI Parameter Value
N12:6
08FC
Data = 2300 (8FC hex) = 230.0V AC
n/a
Address
Value (hex)
Description
See Page
N13:0
0002
Length of Message = 2 bytes
N13:1
0000
The Message was Successful
N13:2
0000