beautypg.com

Chapter 4, Using discrete and block transfer i/o, About i/o – Rockwell Automation 20-COMM-R Remote I/O Adapter User Manual

Page 37: About i/o -1, Using discrete and, Block transfer i/o, Using discrete and block, Transfer i/o, 4using discrete and block transfer i/o

background image

20-COMM-R Remote I/O Adapter User Manual

Publication 20COMM-UM004D-EN-P

Chapter

4

Using Discrete and Block Transfer I/O

This chapter provides information and examples about using I/O to control
a connected PowerFlex drive.

About I/O

I/O is used to transfer the data which can control the PowerFlex drive and its
speed. It is also used for transmitting data through Datalinks.

The Remote I/O adapter uses Discrete I/O and Block Transfer I/O to
transfer I/O data. The ‘Discrete I/O’ is either 1/4 rack (two 16-bit words) or
1/2 rack (four 16-bit words). The rack size is set using Configuration DIP
Switch SW4 or, if the hardware switches have been disabled, adapter
Parameter 27 - [Rack Size]. The ‘Block Transfer I/O’ includes all Block
Transfer Read or Block Transfer Write messages that are 18 words or fewer.

The type of I/O that is transmitted between the drive and controller is set in
Parameter 12 - [DPI I/O Cfg]. When you set up your I/O, note the
following:

• The Logic Command/Status is always transmitted in the discrete I/O.

• The Reference is transmitted in the Discrete I/O if you are using a 1/2

rack, or in the Block Transfer I/O if you are using a 1/4 rack.

• Datalinks are always transmitted in the Block Transfer I/O.

Topic

Page

About I/O

4-1

Understanding the I/O Image

4-2

Discrete I/O Image

4-4

Block Transfer I/O Image

4-7

Example Ladder Logic Program Information

4-11

ControlLogix Controller Example

4-12

PLC-5 Controller Example

4-15

SLC 500 Controller Examples

4-17