SDC S6000KDE DELAYED EGRESS DEVICE User Manual
Page 6
*
Deleting a User (Option 2)
To add a user:
Press 2# User Number (2 digits)# .
For example: 2# 05#
deletes user 5.
*
*
Erase All Users (Option 8)
To
ERASE ALL USERS!!
Press 8# .
All users are erased and the Default Master Code is reset to 1234.
KP
RST
C
NO
C
NO
C
NO
TRIG
REX
RESET
*
Returning the Keypad to Factory Default Settings
Short the KP RST terminal located on the main controller board.
Press 99# 1234 8# .
Press 3#1#2# . Sets the Output #1 (Reset) for 2 seconds.
Press 3#2#2# . Sets the Output #2 (Auth Exit) for 2 seconds.
Press 3#3#0# . Sets the Output #3 (Bypass) for latching.
Press 1#02#11#2# . Adds user # 2 with a code of 11. [Reset]
Press 1#03#22#3# . Adds user # 3 with a code of 22. [Auth Exit]
Press 1#04#33#4# . Adds user # 4 with a code of 33. [Bypass]
Press to exit programming mode.
Remove the shorting jumper from the KP RST terminal.
*
*
*
*
*
*
*
**
*
Entering Programming Mode
Press 99# Master Code .
For example: 99# 1234
Enters programming mode using the Default Master Code.
*
**
Exit Programming Mode
Press .
*
*
**
*
*
Changing the Master Code
User 1 is always used as the Master Code and is required to access keypad programming. The Factory
Default Master Code is “1234 ”. It is strongly recommended that a new Master Code is assigned after
installation. WRITE DOWN THE NEW CODE. If the master code is lost, you must use the keypad reset jumper
on the main circuit board to enter programming mode by using the Default Master Code.
To Change the Master Code (User 1)
1) Enter Programming Mode: Press 99# Master Code .
2) Assign new Master Code : Press 1# 01# New Pin Code# Output Relay # .
For example: 99# 1234 1# 01# 3871# 0#
changes the Master code from 1234 to 3871.
3) Press to exit programming mode.
*
Adding a User / Changing User Pin Codes (Option 1)
To add a user:
Press 1# User Number (2 digits)# New Pin Code# Output Relay # .
For example: 1# 05# 55# 2#
adds user 5's pin code as one that will activate authorized exit.
*
Output Relay Codes
2= Reset
3= Authorized Exit
4= Bypass
P:\INSTALLATION INST\Delayed Egress\INST-S6000DE_KDE_MOD.vsd Rev -2 08-12 Page 6