beautypg.com

Input and output ratings, Display, Power supply – SATEC PM296 User Manual

Page 72: Environmental conditions

background image

Appendix: Technical Specifications

64

Input and Output Ratings

Current input
terminal

Rated 10A 250V Pitch 10 mm
Wire 3 mm

2

(10 AWG)

Voltage input
connector

Rated 32A 690V Pitch 9.5 mm
Wire max. 4 mm

2

(10 AWG)

Communications Two optically isolated serial ports:

COM1 RS-232 (9-pin D-type connector)
COM1 RS-485 (3-pin connector)
COM2 RS-422/RS-485 (5-pin connector)

Service terminals Standard 5 mm pitch (UL recognized 7463)

SCREW M3
Maximum wire diameter 2.05 mm (12 AWG)

Display

Display High-brightness

seven-segment digital LEDs, 11 windows.

A total of 55 pages on two page levels with simultaneous display up
to 11 parameters.

Real-time clock

Accuracy: about 1 minute per month @ 25

°

C

Power Supply

Galvanically
isolated power
supply

Manufacturer’s spec.
85-265V AC 50/60 Hz and
88-290 V DC, 18VA
Low DC voltages:
12V (9.6-19), 12W
24V (19-37), 12W
48V (37-72), 12W

UL Rating

95-264 VAC 50/60 Hz and
90-290 V DC, 10W
Low DC voltages:
12V (9-18)
24V (18-36)
48V (36-72)

CATEGORY

II

POLLUTION DEGREE

2

(IEC 664)

Environmental Conditions

The instrument has been designed to be safe at least under the following conditions:

-

indoor use

-

altitude up to 2000m

-

temperature 5°C to 40°C

-

maximum relative humidity 80% for temperatures up to 31°C decreasing linearly
to 50% relative humidity at 40°C

-

mains supply voltage fluctuations not to exceed ±10% of the nominal voltage

-

transient overvoltages according to

INSTALLATION CATEGORY

II

-

POLLUTION DEGREE

2 in accordance with IEC 664

Operating
temperature

-20°C to 60°C (-4°F to 140°F)

(COM1: only one line