Chapter 4 Setup Menus

28

parameter. For signed (bi-directional) values, such as powers and signed power factor,
the scale is always symmetrical with regard to 0 mA, and the full scale corresponds to
+1 mA output for positive readings and to -1 mA output for negative readings. For
these, the zero scale (0 mA output) is permanently set in the instrument to zero for all
parameters except the signed power factor for which it is set to 1.000, and may not
change. Unsigned parameters are output within the current range 0 to +1 mA and can
be scaled using both zero and full scales as in the case of single-ended analog output.

4.

When the analog scale value exceeds the number of places in the window, it is

converted to higher units (for instance, kW to MW) and a decimal point is placed in the
window to indicate the new measurement range.

5.

Each time you select the output parameter for the analog channel, its zero and full

scales are set by default to the lower and upper parameter limits, respectively.

Table 4-3 Analog Output Setup Options

Code Option Description

OutP

Output parameter

The output parameter for the analog output
channel

Lo

Zero scale (0/4 mA)

The reading of the parameter corresponding to
a zero-scale current output

Hi

Full scale (1/20 mA)

The reading of the parameter corresponding to
a full-scale current output

Table 4-4 Analog Output Parameters

Code Parameter Unit Scale

none Output

disabled

0

Real-time Measurements

rt U 1

Voltage L1/L12

V/kV

0 to Vmax

rt U 2

Voltage L2/L23

V/kV

0 to Vmax

rt U 3

Voltage L3/L31

V/kV

0 to Vmax

rt U.L12

Voltage L12

V/kV

0 to Vmax

rt U.L23

Voltage L23

V/kV

0 to Vmax

rt U.L31

Voltage L31

V/kV

0 to Vmax

rt C1

Current L1

A

0 to Imax

rt C2

Current L2

A

0 to Imax

rt C3

Current L3

A

0 to Imax

thd.U1

Voltage THD L1/L12

%

0 to 999.9

thd.U2

Voltage THD L2/L23

%

0 to 999.9

thd.U3

Voltage THD L3

%

0 to 999.9

thd.C1

Current THD L1

%

0 to 999.9

thd.C2

Current THD L2

%

0 to 999.9

thd.C3

Current THD L3

%

0 to 999.9

tdd.C1

Current TDD L1

%

0 to 100.0

tdd.C2

Current TDD L2

%

0 to 100.0

tdd.C3

Current TDD L3

%

0 to 100.0

HFc.C1

Current K-Factor L1

1.0 to 999.9

HFc.C2

Current K-Factor L2

1.0 to 999.9

HFc.C3

Current K-Factor L3

1.0 to 999.9