SATEC PM296 User Manual
Page 29
Chapter 4 Setup Menus
21
Table 4-1 Basic Setup Options
(
∗ default setting
)
Code Parameter Options Description
ConF
Wiring mode
3OP2
3-wire open delta using 2 CTs
(2 element)
4Ln3
∗
4-wire Wye using 3 PTs (3 element), line to
neutral voltage readings
3dir2
3-wire direct connection using 2 CTs (2
element)
4LL3
4-wire Wye using 3 PTs (3 element), line to
line voltage readings
3OP3
3-wire open delta using 3 CTs
(2½ element)
3Ln3
4-wire Wye using 2 PTs (2½ element), line to
neutral voltage readings
3LL3
4-wire Wye using 2 PTs (2½ element), line to
line voltage readings
Pt
PT ratio
1.0
∗ -
6,500.0
The phase potential transformer ratio
Ct
CT primary current
1-5000A
(5
∗)
The primary rating of the phase current
transformer
Ct.Au
Auxiliary CT primary
current
1-5000A/mA
(5000
∗)
The primary rating of the auxiliary current
transformer
dc.OF DC voltage zero
offset
0-9999 (0
∗) The reading of the DC voltage corresponding
to a zero DC voltage input
dc.FS DC voltage full scale
reading
0-9999 (20,
100, 300
∗)
The reading of the DC voltage corresponding
to a full-scale DC voltage input. By default it is
set to the DC full-scale input (20, 100 or 300
VDC)
d.P
Demand period
1, 2, 5, 10,
15
∗, 20, 30,
60, E
The length of the demand interval (sub-interval
for sliding window demand) for power demand
calculations, in minutes. E = external
synchronization
n.dp
Number of demand
periods
1-15
(1
∗)
The number of demand sub-intervals to be
averaged for sliding window demands. A
product of the demand period and the number
of demand periods should not exceed 60 min.
For block demand, set this value to one.
A.dP
Ampere/Volt
demand period
0-1800s
(900
∗)
The length of the demand period for
volt/ampere demand calculations, in seconds
0 = measuring peak current
t.con Thermal demand
time constant
1-3600.0 s
(195.4
∗)
The simulated thermal element time constant
for thermal demand measurements
buF
Averaging buffer
size
8
∗,16,32
The number of measurements for RMS sliding
averaging
rSt
Reset enable/disable diS, En
∗
Protects all reset functions, both via the front
panel or communications.
PrE.C
The number of pre-
event cycles for the
waveform recorder
1-8 (1*)
The number of waveform cycles to be recorded
before the event that triggered waveform
capture