Reset menu, Electrical installation, 13 reset menu – SATEC PM296 User Manual
Page 47
Chapter 4 Setup Menus
39
4.13 Reset Menu
This menu allows you to reset to zero the accumulators and Min/Max registers in
your instrument. The menu can be only accessed via the Setup Change Menu
(CHG)
. If the reset is disabled from the Basic Setup Menu (see Section 4.1), you
will not be able to enter this menu.
The following designations are used in the menu to specify a data location to be
reset:
A.dnd
Resets volt/ampere maximum demands
P.dnd
Resets total power maximum demands
dnd
Resets all total maximum demands
EnrG
Resets total energies
Lo.Hi
Resets Min/Max registers (does not affect maximum demands)
tOU.E
Resets the TOU energy registers
tOU.d
Resets the TOU maximum demand registers
Cnt
Resets all pulse counters
Cnt.1 -
Cn.16
Resets counter # 1- #16
To reset the desired locations:
Press to activate the middle window, and then use the up/down arrow keys to
scroll to the desired data location entry.
Press to activate the lower window.
Press and hold for about 5 seconds until the do label is replaced with done,
and then release the key. You will return to the middle window.
To quit the reset menu:
Press .
NOTE
If changing data in the instrument via the front panel is not secured by a password, the fast
reset of the Min/Max registers, maximum demands and total energies can be made from the
data display mode (see Section 5.1) and counters from the Status Information Menu (see
Section 6.1) without entering the reset menu.
rSt
do
EnrG
SELECT
ESC
ENTER
SELECT
SELECT
CHG
rSt
ENTER
ENTER