4.7 Pulsing Output Setup Menu
This menu allows you to program either of the six relays provided by your
PM296/RPM096
instrument to output energy pulses. Available pulsing
parameters are listed in Table 4-5.
To select a pulse relay:
Use the up/down arrow keys to scroll to the desired relay. The pulsing
parameter assigned to the relay is displayed in the middle window, and
the amount of unit-hours per pulse is displayed in the lower window.
To change the pulse relay setup:
Press to activate the middle window.
Use the up/down arrow keys to scroll to the desired output parameter.
Selecting nonE disables pulsing through this relay.
Press to activate the lower window.
Use the up/down arrow keys to set the amount of unit-hours per pulse.
The available range is 1-9999.
Press to store the new setup, or press to quit the setup
without changes.
To quit the pulsing setup menu:
From the upper window, press or .
Table 4-5 Pulsing Output Parameters
Code Parameter
nonE Output
disabled
Ac.Ei
kWh import (positive)
Ac.EE
kWh export (negative)
Ac.Et
kWh total (absolute)
rE.Ei
kvarh import (inductive)
rE.EE
kvarh export (capacitive)
rE.Et
kvarh total (absolute)
AP.Et
kVAh total
NOTES
1. You will not be able to store your setup in the instrument if you assigned a parameter to
relay output with a zero number of unit-hours per pulse, or if the parameter you selected
has just been assigned to another relay output.
2. If a relay you allocated for pulsing has been manually operated or released, it reverts
automatically to normal operation.
3. If a relay you allocated for pulsing has been engaged by an alarm/event setpoint, the
setpoint is automatically disabled.
rEL.1
1
Ac.Ei
ESC
ENTER
SELECT
SELECT
ENTER
ESC
SELECT
CHG
PulS
ENTER
ENTER